Refrigerants Recessed Value
Versatile Safety Features
- Audible buzzer alarm
- End-of-life indication for sensor element
- Buzzer test button for safety checks
- Relay output for alarm indication
Superior Sensing
- 10 year life expectancy on elements
- Calibration mode makes calibration quick and easy
- Ideal for hotels
Simple and versatile
- Fits easily in standard single gang boxes
- 45 degree terminals for ease of wiring
- Saves installation time and reduces callbacks
Choose from a range of options
- 0-5V, 0-10V, and 3-wire 4-20mA options
- Thermistor outputs for temperature optional
Versatile Safety Features
- Audible buzzer alarm
- End-of-life indication for sensor element
- Buzzer test button for safety checks
- Relay output for alarm indication
Superior Sensing
- 10 year life expectancy on elements
- Calibration mode makes calibration quick and easy
- Ideal for hotels
Simple and versatile
- Fits easily in standard single gang boxes
- 45 degree terminals for ease of wiring
- Saves installation time and reduces callbacks
Choose from a range of options
- 0-5V, 0-10V, and 3-wire 4-20mA options
- Thermistor outputs for temperature optional
SPECIFICATIONS |
Power Supply |
|
12-30VDC/24VAC (1), 24mA max. |
Outputs |
Options |
0-10V, 0-5V, 2-wire or 3-wire 4-20mA (selectable) |
Refrigerant output scaling |
0-1000 ppm |
Alarm Relay |
Relay characteristics |
N.C. 1A@24/30VDC (50/60Hz) (no mains connection) |
CO alarm setpoint |
Activates above 300ppm |
LEDs |
LED indicator Refrigerant |
1 long blink above 300PPM, 1 short blink above 600 ppm |
End-of-life Indicator |
3 blinks at 30s intervals3 blinks at 30s intervals |
Audible Alarm |
Audible Buzzer Refrigerant |
Activates above 300ppm for 1 hour or 600 ppm for 15 min |
Alarm Test |
Hidden button provided for buzzer test |
Refrigerant Sensor Performance |
Type |
MOS |
Resolution |
1ppm |
Life expectancy |
>10 years |
Calibration(2) |
Calibrated to R134A refrigerant |
Sensitivity |
@300ppm test gas: 450ppm R410A, 425 ppm R407C, 400ppm R404A, 370ppm R22, 300ppm R134A |
Other detectable gases(3) |
R407A, R407F, R427A, R452B, R507, R448A, R449A, R422A, R422D, R452A, R513A, R514A, R32 |
Coverage Area |
5000-7500 square feet |
Calibration Interval |
6 months, hold test button for 10s to enter cal mode |
Enclosure |
Dimensions |
4.45”h x 2.7”w x 0.5”d (depth measured from wall) |
Temp Rating |
-20 to 50C operating |
Compliance |
|
CE, RoHS |
- One side of transformer, secondary is connected to signal common. Dedicated transformer is recommended. 15-30VDC/24VAC power supply voltage required for 10 volt output.
- R134A sensor is factory calibrated to R134A gas but may be used as a general purpose refrigerant sensor. Sensitivity to some other gases can be found here . Actual response may vary depending on installation. For more accurate response to a specific gas, a unit may be field calibrated.
- These gases my be detected by the sensor but sensitivity curves are not available at this time.