Key Points
- Adjustable for ranges of 2000, 5000, or 10,000 ppm CO2
- Field replaceable NDIR element
- Dual 3-wire 4-20mA and 0-5/0-10V (selectable)
Applications
- Controlling ventilation in response to occupancy
- Facilitates compliance with ASHRAE 62.1 standard for air quality
- Offices, conference rooms, and public assembly areas
Featuring a gold plated self-calibrating NDIR sensor for high accuracy. A built-in LCD display makes set up a snap, and a standard solid-state setpoint relay makes demand ventilation simple. Dual 4-20mA and 0-10/5 vdc outputs.
Easy to install and maintain
- Integrated display and push-button menus for field selectable scale, calibration, and operational modes
- Dual 4-20mA and 0-5V/0-10V output (jumper selectable)
- Integrated high-reliability solid-state set-point relay is ideal for direct control applications; easy to set up thanks to LCD
High reliability reduces call backs
- Non-dispersive infrared sensing element (NDIR)
- Field replaceable CO2 sensor
- 15+ year life expectancy on CO2 sensing element
- Industry leading 7-year limited warranty on electronics; NDIR module 3 years
High accuracy for improved system performance
- Internal heater for reliable outdoor operation
- Selectable auto-calibration mode returns sensor to baseline values
- ±40ppm, ±3% of reading
SPECIFICATIONS |
Power Supply |
|
12-30VDC/24VAC(1), 100mA max. |
Analog Outputs |
Dual Analog |
3-wire 4-20mA and 0-5V/0-10V (2) (jumper) |
Output scaling |
0 - 2000 or 0 - 5000 ppm (selectable) |
Digital Setpoint Output |
Programmable |
Solid-state, 1A @ 30VAC/DC, N.O. |
Sensor Performance |
Type |
Non-dispersive Infrared (NDIR) |
Accuracy |
±30ppm, ±3% of reading (400-2000ppm) ±50ppm, ±5% of reading (2000-5000ppm) |
Response time |
60 seconds to 90% reading |
Output update rate |
1 second |
LCD Menu Setup Parameters |
SPH, Setpoint, Hi (On point) |
500ppm to full-scale (800ppm default) |
SPL, Setpoint, Lo (Off point) |
400ppm to full-scale-50 (700ppm default) |
SCL, Scaling |
0-2000ppm or 0-5000ppm |
(2000ppm default) |
ADJ, Adjustment |
Offset adjustment +/-250ppm (0 default) |
CAL, Calibration mode |
Automatic mode ON or OFF (default=ON) |
RUN, Run mode |
Displays CO2 in ppm |
Operating Environment |
Temperature |
-4 to 122F (-20 to 50C) |
Humidity |
0-95% non-condensing |
Enclosure |
Material |
Polycarbonate; aluminum tube |
|
Dimensions |
4.0”h x 4.4”w x 2.1”d |
- One side of transformer secondary is connected to signal common. Dedicated transformer is recommended.
- 15-30VDC/24VAC power supply voltage required for 10 volt output.