Page 91 - 2020 Catalog
P. 91

AIR QUALITY



          ORDERING                                 SPECIFICATIONS
              Pkg  Out  Gas1  Gas2  Temp  Lid  Power Supply                     15-30VDC/24VAC , 4W max, 160mA max.
                                                                                           (1)
               TG                 -                          2 programmable outputs  0-10V (default), 0-5V, 1-5V, 4-20mA (menu selectable)  AIR QUALITY
                                           Analog Outputs           Output scaling  0-1000ppm (default), 0-1000ppm (menu selectable)
       Package
                                                                                      o
       W = Wall Mount                                       Temperature output scaling  -20 to 85 C
       M = Metal                                                    Protocol RS-485  BACnet MS/TP, Modbus RTU, Modbus ASCII
       D = Duct Mount                      BACnet /Modbus              Baud Rates  9600, 19200, 38400, 57600, 76800, 115200
       Output Type                         Fan Relay          Fan relay characteristics  N.C. 1A@24/30VDC (50/60Hz) (no mains connection)
       A = Analog                                                 Fan relay setpoint  300 ppm (default), 0-1000 ppm (menu selectable)
       B = BACnet/Modbus                                     Alarm relay characteristics  N.C. 1A@24/30VDC (50/60Hz) (no mains conenction)
                                           Alarm Relay
       Gas Type 1*                                               Alarm relay setpoint  600 ppm (default), 0-1000 ppm (menu selectable)
       A = Ammonia                         Display                  3-1/2 digit LCD  Indicates gas concentration in ppm (menu selectable)
       2 = R22                             LEDs                   Green, Yellow, Red  Green = Normal, Yellow = Relay, Red = Alarm  Toxic Gas Series
       3 = R134A  (Multi-Gas)
       4 = R410A                           Audible Alarm       85dB Piezo transducer  30 minutes above alarm setpoint (menu selectable)
       5 = R404A                                                           Type  MOS
       6 = R407C                                                   Detection Range  0-1000 ppm
       C = CO                                                          Resolution  1 ppm
       N = NO2
                                                        R22, R134A, R410A, R404A, R407C Calibrated for respective gas
       Gas Type 2                          General
       X = No second gas                   Purpose Sensor         R134A Sensitivity(2)  @300ppm test gas: 450 ppm R410A, 425 ppm R407C,
       A = Ammonia                         Performance                          400 ppm R404A, 370 ppm R22, 300 ppm R134A
       2-6 = Refrigerants (See above)                         Other detectable gases(3)  R407A, R407F, R427A, R452B, R507, R448A, R449A,
       Temperature Output                                                       R422A, R422D, R452A, R513A, R514A, R32
       A = None                                                     Life expectancy  >10 years (typical life expectancy for MOS sensors)
       C = 100Pt RTD                                                Coverage Area  5000-7500 square feet
       D = 1000Pt RTD                                                      Type  Electrochemical
       E = 10K Type 2                                                   Accuracy  ±5% of default range
       F = 10K Type 3                      Ammonia Sensor              Resolution  0.1ppm
                                           Performance
       G = 10k w/11k                                                Life expectancy  5 years
       H = 3k                                                       Coverage Area  5000-7500 square feet
       I = 2k2                                                             Type  Electrochemical
       J = 1k8                                                          Accuracy  ±5% of default range  ±5%of reading above 200ppm
                                                                                              (2)
       Enclosure Lid                       CO Sensor                   Resolution  1ppm
                                           Performance
       Blank = Clear/Tinted                                          Certifications  UL2034 Listed Component
       S = Solid/Opaque                                             Life expectancy  >7 years
       W=All White Solid
                                                                    Coverage Area  5000-7500 square feet
       Replacement Elements                                                Type  Electrochemical
       TGS-A-UL = Ammonia                                               Accuracy  ±5% of default range  ±5%of reading above 20ppm
                                                                                              (3)
       TGS-2-UL = R22                      NO2 Sensor                  Resolution  0.1ppm
                                           Performance
       TGS-3-UL = R134A (multi-gas)                                 Life expectancy  >7 years
       TGS-4-UL = R410A         warranty                            Coverage Area  5000-7500 square feet
       TGS-5-UL = R404A                                      Temperature, continuous  -20 to 50 C
                                                                                      o
       TGS-6-UL = R407C                    Operating                    Humidity  15-95% continuous, 0-95% intermittent
                                           Environment
                                                                     Max Elevation  2000m
            Scan here to see                                             Material  ABS/Polycarbonate
           refrigerant cross-              Enclosure                  Dimensions  4.0”h x 4.4”w x 2.1”d
              sensitivities                (Wall & Duct)           Conduit Opening  Tapped 1/2” NPT
                                                                          Rating  IP20
                                                            Material & Enclosure Rating  Powder coated steel/acrylic, NEMA 3R
                                                                      Dimensions  5.0”h x 4.3”w x 2.25”d
                                           Enclosure
                                           (Metal)                      Opening  Dual air vents on bottom of enclosure
                                                                        Mounting  Pre-drilled for 2x4” electrical box
                                                                          Rating  IP20
                                           Agency                     Compliance  UL61010-1 Listed UL, cUL, CE
     (1) One side of transformer secondary is connected to signal common. Dedicated transformer is recommended. No mains circuit connection allowed.  In addition, it is required
     to use an isolated power supply that is certified by a national or international standard (i.e. UL).  Use of a Class 2 LPS power supply or greater is required.
     (2) R134A sensor is factory calibrated to R134A gas but may be used as a general purpose refrigerant sensor.  Sensitivity to some other gases can be found in the installation
     manual.  Actual response may vary depending on installation.  For more accurate response to a specific gas, a unit may be field calibrated.
     (3) These gases my be detected by the sensor but sensitivity curves are not available at this time.
                                                           Higher Reliability, Faster Installation, Superior Accuracy   |  Sense the difference   |  91