Page 9 - 2020 Catalog
P. 9
CURRENT
SPLIT CORE OPTIONAL RELAY SPLIT CORE - MINI SOLID CORE SOLID CORE - MINI
C-2320 for additional labor savings C-2220 C-1320 C-1220
Aperture (A)
Aperture (A) CURRENT
H
W
L PreSet™ Series
L: 2.5” H: 0.57” W: 2.23” L: .84" H: .72” W: 2.06" L: 2.00” H: .75” W: 1.75” L: 2.40" H: 1.04" W: 1.6" L: 1.91" H: .88" W: 1.31"
A: 0.75"x 0.75" A: .0.40”x 0.32” A: 0.52” diameter A: 0.30” diameter
▪ Mount sensor without ▪ Add to 2320 series to ▪ Mount sensor without ▪ Compact design ▪ Super small—fits
removing conductor for get start/stop/status in a removing conductor for ▪ Aperture accomodates anywhere
installation savings single device installation savings spade terminals ▪ Low cost
▪ Clamp on conductor with ▪ Reduces the number of ▪ Fits in small enclosures
iris, or use detachable installed components... ▪ Clamp on conductor with
base to screw or DIN saves time and space iris, or screw mount
mount ▪ Removable relay facilitates detachable base
▪ Larger 0.75” aperture service
accomodates oversize
conductors
ORDERING INFORMATION SPECIFICATIONS
Min
SPLIT CORE (on) Max N.O. Output* Trip Power Standard Output Rating 1.0A@30VAC/DC
LED
LED
A
C-2320-L 0.45A 50A 1.0A@30VAC/DC • • Line Voltage Output Rating 0.2A@120VAC (-HV ONLY)
Output Type NO, solid-state FET
C-2320 0.50A 100A 1.0A@30VAC/DC • •
NEW Temperature Rating -15-60 ° C
C-2320-H LOWER 0.50A 150A 1.0A@30VAC/DC • •
TURN-ON! 600V RMS. For use on insulated
C-2320HV 0.50A 100A 0.2A@120VAC • • Insulation Class conductors only! Use minimum
C-2320HV-L 0.45A 50A 0.2A@120VAC • • 75 ° C insulated conductor
Sensor Power Induced
SPLIT CORE - MINI
Frequency Range 50/60Hz
C-2220 1.00A 50A 1.0A@30VAC/DC •
Compliance cUL, UL, CE, RoHS
SOLID CORE
TYPICAL WIRING
C-1320 0.75A 50A 1.0A@30VAC/DC •
SOLID CORE - MINI CONTROLLER NOTE: Device is NOT polarity sensitive. INSULATED PRIMARY
V+ AC CONDUCTOR
V+
C-1220-L 0.75A 5A 1.0A@30VAC/DC • 600VAC MAX
v
DI
C-1220 0.75A 50A 1.0A@30VAC/DC • DI 40
20 30 50 60
C-1220HV-L 0.75A 5A 0.2A@120VAC • 10 70 85 Set knob
to motor
Status Output
1.0A @ 30VAC/DC HI LO 1 100 FLA
C-1220HV 0.75A 50A 0.2A@120VAC • Normally Open Output closed above 70% of FLA
(SINKING)
ALTERNATE
COMMAND RELAY Contact rating Coil CONTROLLER ARRANGEMENTS
V+
CR3-24 N.O. 10A @ 125VAC 24VAC/DC 15mA nom.
DI DI
CR4-24 N.C. 10A @ 125VAC 24VAC/DC 15mA nom. VAC
DI DI 24VAC
CR3-12 N.O. 10A @ 125VAC 9-12VDC 30mA nom. GND
CR4-12 N.C. 10A @ 125VAC 9-12VDC 30mA nom.
(SOURCING) (AC)
Warning: Refer to installation instructions that
Other coil voltages available—consult factory
accompany product and heed all safety instructions.
Ordering tip: For best resolution, choose the sensor lowest Do not rely on current status LED to indicate presence
maximum amperage which accomodates your motor (e.g. 0-50A us
-L, 50-100A use standard, 100 to 150A use -H
7 year limited warranty
PROUDLY MADE IN USA
Higher Reliability, Faster Installation, Superior Accuracy | Sense the difference | 9